8.0 Measurement and Test Protocol
Test protocol according to VDE 0113/EN 60204, BGV A3
Test Protocol No.:
Order No. and/or Description:
Reason for Test
|
|
|
|
|
Inspection:
|
|
|
|
|
|
|
|
|
|
|
|
Measurements, testing performed on:
Measuring device used according to DIN VDE: Multimeter / Insulation tester
If multiple measurement results are obtained for the same test, always record the worst result!
Continuity of protective conductor system
Test current at least 10A/50Hz. The test must be performed between the PE terminal and various points that are part of the protective conductor system.
Limit Values |
Cross Section |
Max Voltage Drop |
Compliant Enter value! |
Non-compliant Enter value! |
(corresponding |
1.0 mm² |
3.3V |
----------- |
----------- |
Cross section |
1.5 mm² |
2.6V |
----------- |
----------- |
mark!) |
2.5 mm² |
1.9V |
----------- |
----------- |
4.0 mm² |
1.4V |
----------- |
----------- |
|
>6 mm² |
1.0V |
----------- |
----------- |
Insulation Resistance
Measured with 500V DC between the conductors of the power circuits and the protective conductor system.
Caution: Disconnect machine/system from mains, do not touch test probes!
Measured value must be >1M?!
Measurement |
Compliant - Enter Value! |
Non-compliant - Enter Value! |
L1-PE |
---------------------- |
---------------------- |
L2-PE |
---------------------- |
---------------------- |
L3-PE |
---------------------- |
---------------------- |
N-PE |
---------------------- |
---------------------- |
If safety measurements are compliant, the system can now be connected to mains voltage!
Caution with the following voltage measurements!!!
Input Voltages
Measured with voltage measuring instrument between the phases and between phases and neutral conductor.
Measurement |
Value |
Measurement |
Value |
L1-L2 |
------------------------- |
L1-N |
------------------------- |
L2-L3 |
------------------------- |
L2-N |
------------------------- |
L1-L3 |
------------------------- |
L3-N |
------------------------- |
Control Voltages
Measured with voltage measuring instrument. Record measurement location and value (e.g., transformer input, transformer output, PLC power supply DC voltage, etc.).
Measurement Location |
Value |
------------------------------------------------------- |
------------------------- |
------------------------------------------------------- |
------------------------- |
------------------------------------------------------- |
------------------------- |
------------------------------------------------------- |
------------------------- |
------------------------------------------------------- |
------------------------- |
Testing:
Testing refers exclusively to the safety devices listed below and is not a general functional test.
Execution of Measurements:
Name Date Signature